Calculates minimum cross-section and maximum cable length taking into account the voltage drop
Fill in the fields below and click "Calculate".
Cable dimensioning: calculating the cross-section and length
The correct dimensioning of electrical cables is relevant to safety and economically important. Our calculator determines:
- Minimum cross-section: According to current carrying capacity (DIN VDE 0298-4)
- Voltage drop: Max. 3% for lighting, 5% for devices
- Maximum cable length: For a given cross-section
- Fuse protection: Suitable fuse/circuit breaker
- Type of installation: Overhead line, pipe, bundle (correction factors)
Current carrying capacity according to VDE (copper, 3 cores in conduit, 30°C):
- 1.5 mm²: 13.5 A (lighting, sockets)
- 2.5 mm²: 18 A (sockets, stove connection)
- 4 mm²: 25 A (electric stove, instantaneous water heater)
- 6 mm²: 32 A (stove, sauna)
- 10 mm²: 44 A (meter connection, distributor)
Important: Note correction factors! The load capacity decreases with increased ambient temperature, bundled cables or different installation methods. Fuse rating must be lower than load capacity: 16A fuse for 1.5mm² (13.5A load capacity) is WRONG! Correct: 13A or 10A.
Voltage drop: ΔU = 2 × I × L × 0.0178 / A (for copper). For long cables, the cross-section must be increased, even if the current carrying capacity is sufficient. Example: 50m cable, 16A, 2.5mm²: ΔU = 11.4V (5%) - borderline!