Cable Cross-Section Calculator

Electricity
15,549 calculations
Having trouble? Go to tutorial
📝 How it works:
Calculate the required cable cross-section according to DIN VDE 0298-4 and DIN VDE 0100-520. Considers cable length, voltage, current, installation type and material (copper/aluminium).

Fill in the fields below and click "Calculate".

Cable Cross-Section Calculator

Determine the correct cable cross-section for your electrical installation quickly and reliably. Our calculator uses DIN VDE 0298-4 and DIN VDE 0100-520 to give you accurate results.

How to Use

Enter the current type, voltage, current strength, cable length and installation type. The calculator instantly shows the required minimum cross-section.

Why Correct Cable Sizing Matters

  • Prevents overheating and fire hazards
  • Ensures compliance with DIN VDE standards
  • Optimises energy efficiency
  • Required for installation approvals

Current-carrying capacity by cross-section (copper)

These are the values the calculator uses (copper, three loaded conductors, 30 °C ambient, no grouping), based on the German standard DIN VDE 0298-4. Other countries apply their own tables (e.g. IEC 60364-5-52, BS 7671, NEC) – always check local regulations.

Cross-sectionIn conduitSurface-mountedBuried
1.5 mm²13.5 A17.5 A19 A
2.5 mm²18 A24 A26 A
4 mm²24 A32 A35 A
6 mm²31 A41 A45 A
10 mm²42 A57 A61 A
16 mm²56 A76 A82 A
25 mm²73 A96 A104 A
35 mm²89 A119 A125 A

Maximum cable length at 3 % voltage drop

Same formula as the calculator: L = γ × A × ΔV ÷ (2 × I × cos φ), with √3 instead of 2 for three-phase; copper γ = 56 m/(Ω·mm²), cos φ = 1, ΔV = 3 % of nominal voltage. The current-carrying capacity above must also be sufficient.

ApplicationCurrentCross-sectionMax. length
Socket circuit 230 V16 A2.5 mm²30 m
Cooker circuit 230 V20 A2.5 mm²24 m
EV charger 11 kW, 400 V16 A2.5 mm²61 m
EV charger 11 kW, 400 V16 A4 mm²97 m
EV charger 22 kW, 400 V32 A6 mm²73 m
EV charger 22 kW, 400 V32 A10 mm²121 m

These values are a planning aid. Installation must comply with local wiring regulations and be carried out or checked by a qualified electrician.