Calculate the prospective fault current Ik from the measured loop impedance Zs and verify the disconnection condition per IEC 60364-4-41 for MCBs and RCDs.
Fill in the fields below and click "Calculate".
Calculate the fault current from loop impedance
Every initial verification includes measuring the earth fault loop impedance Zs. The prospective fault current follows from Ik = c × U₀ / Zs, where c = 0.95 accounts for the permitted downward voltage tolerance. This calculator evaluates your measurement and instantly checks the automatic disconnection condition per IEC 60364-4-41.
Disconnection condition
The fault current must trip the protective device within the required time (0.4 s for final circuits up to 63 A). For MCBs per EN 60898-1 the upper magnetic trip limits are B = 5 × In, C = 10 × In, D = 20 × In. A B16 breaker therefore needs at least 80 A of fault current, a C16 already 160 A.
Worked example
Measured: Zs = 0.45 Ω on a socket circuit protected by a B16. Ik = 0.95 × 230 V / 0.45 Ω = 486 A ≥ 80 A – condition met with a wide margin. With a C16 at the end of a long cable and Zs = 1.6 Ω, Ik = 137 A < 160 A – the magnetic trip is not guaranteed. Remedies: larger cross-section, type B characteristic, or an RCD.
Maximum permissible Zs
The calculator also outputs Zs,max = c × U₀ / Ia for direct comparison with your meter reading: 2.73 Ω for a B16, only 1.37 Ω for a C16 (at c = 0.95, 230 V). For gG fuses the trip currents depend on the manufacturer's time-current curve.